How many CFM can a 6 inch duct carry?
A 6 in galvanized duct carries about 111 CFM at a friction rate of 0.1 in.wg/100ft, which is 565 fpm. Stretched flex of the same size carries about 78 before it passes the same friction.
The honest answer is that a duct has no single CFM rating. How much it carries depends on how much friction you are willing to accept, and on the material.
What do the common sizes carry at 0.1?
| Round size | Galv. steel | Duct board | Flex duct | Velocity, galvanized |
|---|---|---|---|---|
| 4 in | 37 CFM | 31 CFM | 26 CFM | 424 fpm |
| 5 in | 68 CFM | 57 CFM | 48 CFM | 499 fpm |
| 6 in | 111 CFM | 94 CFM | 78 CFM | 565 fpm |
| 7 in | 167 CFM | 141 CFM | 119 CFM | 625 fpm |
| 8 in | 240 CFM | 202 CFM | 170 CFM | 688 fpm |
How do you find it in the app?
DuctCalc has no field that solves airflow from a diameter. You work backwards with Check a duct:
- Open Check a duct and tap Round duct.
- Type 6 in Diameter and choose the Material.
- Put a guess in Airflow, say 100, and look at Friction rate: 0.083.
- Raise it until the friction reads the rate you design to. 111 CFM gives 0.101 in.wg/100ft.
- Read Air velocity and the badge for the same answer.
Friction is not the only limit
The velocity matters too. For a Residential · supply-air branch the recommended band is 500 to 700 fpm with a 900 fpm ceiling. In a 6 in round that band is roughly 98 to 137 CFM. Push 150 CFM through and the badge turns amber at 764 fpm; at 200 CFM it reads Over maximum · resize at 1,019 fpm.
So for a 6 in supply branch, plan on about 100 CFM. That is a common sense figure, not a rating on the duct.
Mistakes to avoid
- Reading the 111 as a limit. At 0.2 in.wg/100ft the same duct carries more, and it gets louder.
- Using the galvanized number for flex. Flex drops by about 30 percent in the table above.
- Ignoring the run length. The friction rate is per 100 ft, so a 15 ft stub and a 60 ft run are not the same job.
Questions and answers
How many CFM will a 6 inch flex duct carry?
How many CFM can a 5 inch duct handle?
How many CFM in a 4 inch duct?
Is there a CFM from diameter button?
More DuctCalc guides
- How to calculate duct size from CFM
- Round to rectangular duct equivalent, with real velocities
- Recommended duct velocity: the chart, and checking a real duct
- Flex duct friction loss compared with galvanized and duct board
- CFM per ton: the chart, and the duct size that carries it
- What is friction rate in ductwork, and what does a ductulator do with it?
- All questions about DuctCalc
- Back to DuctCalc