How to calculate duct size from CFM
You need two numbers, the airflow and a friction rate, and the round diameter follows. At 400 CFM and 0.1 in.wg/100ft in galvanized steel the exact answer is 9.7 in, so you order 10 in.
The friction rate is the pressure the duct is allowed to lose per 100 ft. Pick one rate for the whole system and the duct sizes come out consistent. For supply trunks and branches 0.1 is the usual starting point, and DuctCalc fills it in for you.
How do you size a duct from CFM in the app?
- Open the Ductulator tab and make sure Size a duct is selected.
- Pick the Material under the inputs. Galv. steel is the default.
- Type the airflow in Airflow, for example 400.
- Leave Friction rate at 0.1 in.wg/100ft, or type your own design rate.
- Read Required round duct, then the Use stock duct size line below it.
What duct size do 400 and 1,200 CFM need at 0.1 in.wg/100ft?
| Airflow | Exact round | Velocity at exact | Stock size | Velocity at stock | Friction at stock |
|---|---|---|---|---|---|
| 400 CFM | 9.7 in | 781 fpm | 10 in | 733 fpm | 0.086 |
| 1,200 CFM | 14.6 in | 1,028 fpm | 16 in | 859 fpm | 0.064 |
The stock line always rounds up, never down, so the friction rate you end up with is lower than the one you asked for. That is why 10 in at 400 CFM runs at 0.086 and not 0.100.
What if you know the velocity you want?
Tap Velocity above the second field and type a number in Target velocity. At 400 CFM and 700 fpm the exact duct is 10.2 in, which lands on a 12 in stock size at 509 fpm and 0.035 in.wg/100ft. The jump is big because the next stock step after 10 is 12.
Common mistakes
- Sizing to the exact diameter. Nobody sells 9.7 in duct; the number to order is the stock one.
- Leaving the material on Galv. steel when the run is flex. See the flex guide for how much that moves the answer.
- Using a supply rate for a return. Returns are designed lower, 0.05 to 0.08 in the Reference tab, so change Friction rate before you size one.
Fittings, filters and coils are outside this calculation. DuctCalc sizes straight duct at a friction rate and nothing else.
Questions and answers
What size duct do I need for 400 CFM?
What friction rate should I use?
Why does the app show two diameters?
Does it work in metric?
More DuctCalc guides
- Round to rectangular duct equivalent, with real velocities
- Recommended duct velocity: the chart, and checking a real duct
- Flex duct friction loss compared with galvanized and duct board
- CFM per ton: the chart, and the duct size that carries it
- How many CFM can a 6 inch duct carry?
- What is friction rate in ductwork, and what does a ductulator do with it?
- All questions about DuctCalc